# Configuration Manual Please read carefully before starting. Also read the product safety information. ### Wiring and connection The ADI-524 can be powered from a DC power supply in the range of 8-36V. Also, it can be powered from the USB port of a computer or IoT gateway. Both power sources can be connected simultaneously without fear of damage. [![ADI-524-sonnecting-via-usb.png](https://docs.atreyo.in/uploads/images/gallery/2025-04/scaled-1680-/adi-524-sonnecting-via-usb.png)](https://docs.atreyo.in/uploads/images/gallery/2025-04/adi-524-sonnecting-via-usb.png) In order to connect sensors with a 4-20mA output, it is necessary to provide them power in the loop. Here are some possible connection methods. Either the built-in isolated 24V power supply can be used or an external current loop power supply can be used. All current inputs marked as - on the housing are connected together. The isolated 24V, on the other hand, has no galvanic connection to any of the inputs. --- #### Connection Diagrams ##### Built-in 24V Connection of four RTD converters using the built-in 24V power supply. ![ADI-524-conncetion-1.png](https://docs.atreyo.in/uploads/images/gallery/2025-02/scaled-1680-/adi-524-conncetion-1.png) ##### External 24 V Connection of four RTD converters using the external 24V power supply. ![ADI-524-conncetion-2.png](https://docs.atreyo.in/uploads/images/gallery/2025-02/scaled-1680-/adi-524-conncetion-2.png) --- ### Modbus configuration It is necessary to set the serial port parameters and the Modbus address using the DIP switch before powering on the device. (reference table for both are given below)

Make sure to reboot/restart device irrespective of any change in DIP switch to be reflected in hardware

##### MODBUS Serial Port Parameter
ParameterOption/range
Baudrate9600 – 115200 configurable
ata bit8
ParityNone
Stop bit1
--- ##### MODBUS Baudrate Configuration User can set the baud rate using 2 Bit DIP switch. This allows to set baud rate between 9600bps to 115200bps as shown below table.
Baudrate SW1 SW2
9600OFF OFF
19200ON OFF
38400OFFON
115200ONON

After setting up the switch, it is necessary to restart the ADI by disconnecting the power supply and, if using USB power, to disconnect it.

--- ##### MODBUS Address configuration User can set the slave ID address using 4 Bit DIP switch. This allow 0 to 15 different IDs to be set. The number below the switches are added together and the result will be identifier of the device slave ID.
Slave IDSW3SW4SW5SW6
1 OFF OFFOFFOFF
1 ON OFFOFFOFF
2 OFFONOFF OFF
3 ON ON OFFOFF
4 OFF OFFON OFF
5 ON OFFON OFF
6 OFFON ON OFF
7 ON ON ON OFF
8 OFFOFFOFFON
9 ON OFFOFFON
10 OFFON OFFON
11 ON ON OFFON
12 OFFOFFON ON
13 ON OFFON ON
14 OFFON ON ON
15 ON ON ON ON