# Configuration Modbus ##### DIP switch configuration This is DIP switch functions diagram for Modbus RTU configuration. For enable Modbus RTU protocol 1 switch should be in OFF position. [![AMB-8I-4O-DIP-1.png](https://docs.atreyo.in/uploads/images/gallery/2025-03/scaled-1680-/amb-8i-4o-dip-1.png)](https://docs.atreyo.in/uploads/images/gallery/2025-03/amb-8i-4o-dip-1.png) ---
##### Baudrate configuration Baudrate configuration for both Modbus and IEC
SwitchBaudrate
0000 9600
0001 1200
0010 2400
0011 4800
0100 14400
0101 19200
0110 28800
011138400
1000 57600
1001 76800
1010 115200
1011 230400
1100 256000
1101 460800
1110 576000
1111 921600
--- ##### Address configuration for Modbus RTU
SwitchValueModbus Address
000000 1
000011 2
000102 3
000113 4
001004 5
001015 6
001106 7
001117 10
010008 20
010019 30
0101010 40
0101111 50
0110012 60
0110113 70
0111014 80
0111115 90
1000016 100
1000117 110
1001018 120
1001119 130
1010020 140
1010121 150
1011022 160
1011123 170
1100024 180
1100125 190
1101026 200
1101127 210
1110028 220
1110129 230
1111030 240
1111131 250
---