Configuration IEC60870 DIP switch configuration This is DIP switch functions diagram for Modbus RTU configuration. For enable IEC60870 protocol 1 switch should be in ON position. Parity configuration Parity configuration for both Modbus and IEC. Parity Function 00 NONE 01 ODD 10 EVEN 11 NONE Baudrate configuration Baudrate configuration for both Modbus and IEC Switch Baudrate 0000 9600 0001 1200 0010 2400 0011 4800 0100 14400 0101 19200 0110 28800 0111 38400 1000 57600 1001 76800 1010 115200 1011 230400 1100 256000 1101 460800 1110 576000 1111 921600 Address configuration for IEC Switch Value IEC Address 0000 0 1 0001 1 2 0010 2 3 0011 3 4 0100 4 5 0101 5 6 0110 6 7 0111 7 10 1000 8 20 1001 9 30 1010 10 40 1011 11 50 1100 12 60 1101 13 70 1110 14 80 1111 15 90 EC60870-5-101 Implementation Guide Protocol Overview The device implements IEC60870-5-101 protocol with the following key functions: Reading States (Interrogation) C_IC_NA_1 (100) Reading all inputs and outputs states Inputs: 1000-1007 Outputs: 2000-2003 Controlling Outputs Function: C_SC_NA_1 (45) Purpose: Setting individual output states IOA range: 2000-2003 Values: ON (1) / OFF (0) Command Structure General Interrogation Command Type ID: 100 (C_IC_NA_1) Qualifier: 20 Cause of Transmission: 6 (Activation) Common Address: 1 Single Command (Output Control) Type ID: 45 (C_SC_NA_1) Cause of Transmission: 6 (Activation) Common Address: 1 IOA: 2000-2003 Value: 0/1 SCADA system configuration IEC60870-5-101 Protocol Configuration Common Address (ASDU): 1 Frame format: FT1.2 Link Layer Address: according to device configuration I/O Points Configuration: For inputs (8 channels): Type: Single Point Information (M_SP_NA_1) IOA addresses: 1000-1007 Direction: Monitoring (read) For outputs (4 channels): Type: Single Command (C_SC_NA_1) IOA addresses: 2000-2003 Direction: Control (write) Verification: Check if input states are correctly read (IOA 1000-1007) Confirm control operation for each output (IOA 2000-2003) Verify device responds to General Interrogation