Configuration manual

Basic information

AMB-8I-4O is an I/O expander operating over Modbus RTU and IEC60870-5-101 protocol. The first DIP switch is used to switch between Modbus RTU and IEC modes. If it is in position 0, then the AMB is operating in Modbus RTU mode. If it is in position 1, then it works in the IEC protocol. As the two protocols have different functions, the DIP switch is also different. In IEC mode, the last DIP switch is used to change the operating mode from balanced/unbalanced. To save the DIP switch settings in the internal memory, the SAVE button must be pressed.


Configuration

DIP switch configuration

This is DIP switch functions diagram for Modbus RTU configuration. For enable Modbus RTU protocol 1 switch should be in OFF position.

AMB-8I-4O-DIP-1.png

This is DIP switch function diagram for IEC protocol. For enable IEC protocol 1 switch should be in ON position.

AMB-8I-4O-DIP-2.png

Parity configuration

Parity configuration for both Modbus and IEC.

Parity Function
00
NONE
01
ODD
10
EVEN
11
NONE
Baudrate configuration

Baudrate configuration for both Modbus and IEC

Switch Baudrate
0000
9600
0001
1200
0010
2400
0011
4800
0100
14400
0101
19200
0110
28800
0111 38400
1000
57600
1001
76800
1010
115200
1011
230400
1100
256000
1101
460800
1110
576000
1111
921600