Configuration manual
Basic information
AMB-8I-4O is an I/O expander operating over Modbus RTU and IEC60870-5-101 protocol. The first DIP switch is used to switch between Modbus RTU and IEC modes. If it is in position 0, then the AMB is operating in Modbus RTU mode. If it is in position 1, then it works in the IEC protocol. As the two protocols have different functions, the DIP switch is also different. In IEC mode, the last DIP switch is used to change the operating mode from balanced/unbalanced. To save the DIP switch settings in the internal memory, the SAVE button must be pressed.
Configuration
DIP switch configuration
This is DIP switch functions diagram for Modbus RTU configuration. For enable Modbus RTU protocol 1 switch should be in OFF position.
This is DIP switch function diagram for IEC protocol. For enable IEC protocol 1 switch should be in ON position.
Parity configuration
Parity configuration for both Modbus and IEC.
-
Parity Function 00 NONE 01 ODD 10 EVEN 11 NONE Baudrate configuration
Baudrate configuration for both Modbus and IEC
-
Switch Baudrate 0000 9600 0001 1200 0010 2400 0011 4800 0100 14400 0101 19200 0110 28800 0111 38400 1000 57600 1001 76800 1010 115200 1011 230400 1100 256000 1101 460800 1110 576000 1111 921600
-