Configuration manual

Basic information

AMB-8I-4O is an I/O expander operating over Modbus RTU and IEC60870-5-101 protocol. The first DIP switch is used to switch between Modbus RTU and IEC modes. If it is in position 0, then the AMB is operating in Modbus RTU mode. If it is in position 1, then it works in the IEC protocol. As the two protocols have different functions, the DIP switch is also different. In IEC mode, the last DIP switch is used to change the operating mode from balanced/unbalanced. To save the DIP switch settings in the internal memory, the SAVE button must be pressed.


Configuration

DIP switch configuration

This is DIP switch functions diagram for Modbus RTU configuration. For enable Modbus RTU protocol 1 switch should be in OFF position.

AMB-8I-4O-DIP-1.png

This is DIP switch function diagram for IEC protocol. For enable IEC protocol 1 switch should be in ON position.

AMB-8I-4O-DIP-2.png

Parity configuration

Parity configuration for both Modbus and IEC.

Parity Function
00
NONE
01
ODD
10
EVEN
11
NONE

Baudrate configuration

Baudrate configuration for both Modbus and IEC

Switch Baudrate
0000
9600
0001
1200
0010
2400
0011
4800
0100
14400
0101
19200
0110
28800
0111 38400
1000
57600
1001
76800
1010
115200
1011
230400
1100
256000
1101
460800
1110
576000
1111
921600

Address configuration for Modbus RTU
SwitchValueModbus Address
000000
1
000011
2
000102
3
000113
4
001004
5
001015
6
001106
7
001117
10
010008
20
010019
30
0101010
40
0101111
50
0110012
60
0110113
70
0111014
80
0111115
90
1000016
100
1000117
110
1001018
120
1001119
130
1010020
140
1010121
150
1011022
160
1011123
170
1100024
180
1100125
190
1101026
200
1101127
210
1110028
220
1110129
230
1111030
240
1111131
250