Configuration IEC60870
DIP switch configuration
This is DIP switch functions diagram for Modbus RTU configuration. For enable IEC60870 protocol 1 switch should be in ON position.
Parity configuration
Parity configuration for both Modbus and IEC.
Parity | Function |
00 |
NONE |
01 |
ODD |
10 |
EVEN |
11 |
NONE |
Baudrate configuration
Baudrate configuration for both Modbus and IEC
-
Switch Baudrate 0000 9600 0001 1200 0010 2400 0011 4800 0100 14400 0101 19200 0110 28800 0111 38400 1000 57600 1001 76800 1010 115200 1011 230400 1100 256000 1101 460800 1110 576000 1111 921600
Address configuration for IEC
Switch | Value | IEC Address |
0000 |
0 | 1 |
0001 |
1 | 2 |
0010 |
2 | 3 |
0011 |
3 | 4 |
0100 |
4 | 5 |
0101 |
5 | 6 |
0110 |
6 | 7 |
0111 | 7 | 10 |
1000 |
8 | 20 |
1001 |
9 | 30 |
1010 |
10 | 40 |
1011 |
11 | 50 |
1100 |
12 | 60 |
1101 |
13 | 70 |
1110 |
14 | 80 |
1111 |
15 | 90 |
EC60870-5-101 Implementation Guide
Protocol Overview
The device implements IEC60870-5-101 protocol with the following key functions:
Reading States (Interrogation)
- C_IC_NA_1 (100)
- Reading all inputs and outputs states
- Inputs: 1000-1007
- Outputs: 2000-2003
Controlling Outputs
- Function: C_SC_NA_1 (45)
- Purpose: Setting individual output states
- IOA range: 2000-2003
- Values: ON (1) / OFF (0)
Command Structure
General Interrogation Command
Type ID: 100 (C_IC_NA_1)
Qualifier: 20
Cause of Transmission: 6 (Activation)
Common Address: 1
Single Command (Output Control)
Type ID: 45 (C_SC_NA_1)
Cause of Transmission: 6 (Activation)
Common Address: 1
IOA: 2000-2003
Value: 0/1
SCADA system configuration
IEC60870-5-101 Protocol Configuration
- Common Address (ASDU): 1
- Frame format: FT1.2
- Link Layer Address: according to device configuration
I/O Points Configuration:
For inputs (8 channels):
- Type: Single Point Information (M_SP_NA_1)
- IOA addresses: 1000-1007
- Direction: Monitoring (read)
For outputs (4 channels):
- Type: Single Command (C_SC_NA_1)
- IOA addresses: 2000-2003
- Direction: Control (write)
Verification:
- Check if input states are correctly read (IOA 1000-1007)
- Confirm control operation for each output (IOA 2000-2003)
- Verify device responds to General Interrogation