Configuration IEC60870

DIP switch configuration

This is DIP switch functions diagram for Modbus RTU configuration. For enable IEC60870 protocol 1 switch should be in ON position.

AMB-8I-4O-DIP-2.png

Parity configuration

Parity configuration for both Modbus and IEC.

Parity Function
00
NONE
01
ODD
10
EVEN
11
NONE

Baudrate configuration

Baudrate configuration for both Modbus and IEC

Switch Baudrate
0000
9600
0001
1200
0010
2400
0011
4800
0100
14400
0101
19200
0110
28800
0111 38400
1000
57600
1001
76800
1010
115200
1011
230400
1100
256000
1101
460800
1110
576000
1111
921600

Address configuration for Modbus RTU
SwitchValueModbus Address
000000
1
000011
2
000102
3
000113
4
001004
5
001015
6
001106
7
001117
10
010008
20
010019
30
0101010
40
0101111
50
0110012
60
0110113
70
0111014
80
0111115
90
1000016
100
1000117
110
1001018
120
1001119
130
1010020
140
1010121
150
1011022
160
1011123
170
1100024
180
1100125
190
1101026
200
1101127
210
1110028
220
1110129
230
1111030
240
1111131
250

Address configuration for IEC
Switch Value IEC Address
0000
0 1
0001
1 2
0010
2 3
0011
3 4
0100
4 5
0101
5 6
0110
6 7
0111 7 10
1000
8 20
1001
9 30
1010
10 40
1011
11 50
1100
12 60
1101
13 70
1110
14 80
1111
15 90

EC60870-5-101 Implementation Guide

Protocol Overview

The device implements IEC60870-5-101 protocol with the following key functions:

Reading States (Interrogation)
  • C_IC_NA_1 (100)
  • Reading all inputs and outputs states
    • Inputs: 1000-1007
    • Outputs: 2000-2003
Controlling Outputs
  • Function: C_SC_NA_1 (45)
  • Purpose: Setting individual output states
  • IOA range: 2000-2003
  • Values: ON (1) / OFF (0)

Command Structure

General Interrogation Command
Type ID: 100 (C_IC_NA_1)
Qualifier: 20
Cause of Transmission: 6 (Activation)
Common Address: 1
Single Command (Output Control)
Type ID: 45 (C_SC_NA_1)
Cause of Transmission: 6 (Activation)
Common Address: 1
IOA: 2000-2003
Value: 0/1

SCADA system configuration

IEC60870-5-101 Protocol Configuration
  • Common Address (ASDU): 1
  • Frame format: FT1.2
  • Link Layer Address: according to device configuration
I/O Points Configuration:

For inputs (8 channels):

  • Type: Single Point Information (M_SP_NA_1)
  • IOA addresses: 1000-1007
  • Direction: Monitoring (read)

For outputs (4 channels):

  • Type: Single Command (C_SC_NA_1)
  • IOA addresses: 2000-2003
  • Direction: Control (write)

Verification:

  • Check if input states are correctly read (IOA 1000-1007)
  • Confirm control operation for each output (IOA 2000-2003)
  • Verify device responds to General Interrogation